Product Categories
Contact Us

Address:4fl,J building, No.1, North Rd, Shangxue Tech Park Bantian ,Longgang District, Shenzhen,518129, P.R.China

Email: ankasales6@szcaj.com

Tel: +86-755-89603006

Fax: +86-755-89603481

Home > News > Content
Conventional 2 Zone Fire Alarm Control Panel
Edit: ANKA Sci-Tech Co.,Limited    Date: Jun 04, 2016

AC POWER: 90 to 270VAC, 50Hz, 3.0amps.

Wire size:minimum 14AWG(2.0mm2) with 600-volt insulation.

BATTERY: Sealed lead-acid batteries only

Maximum charging circuit: 27.6VDC @ 0.8 amp for normal flat charge.

Maximum battery charger capacity: 18AH battery.

Features

Four to Sixteen style B (Class B) initiating device circuits (IDCs).

All zones accept two-wire smoke detectors and any normally open contact devices.

Zones 1-16 configured as general alarm zones.

All circuits are power-limited and supervised, meeting the latest ULC requirements using fuseless technology.

Two built-in, style Y (Class B) Notification Appliance (signal) circuits (NACs).

NACs may be programmed: silenceable, Non-silenceable, Auto-silence

1.25 amps of NAC power, 3.00 amps of total system power.

Alarm, trouble and supervisory, relay output, 24volt operation.

Resettable four-wire smoke detector power @ 500mA. Non-resettable power @ 500mA

Integral battery charger capable of charging up to 18AH batteries (batteries over 4AH)

Require use of the external battery backbox or ULC listed equivalent).

Disable/enable control per IDC

Reverse polarity protection.


Feedback
ANKA Sci-Tech Co.,Limited
ANKA Sci-Tech Co.,Limited