1. Wired Interconnection Smoke Alarm System Cable Requirements
| Cable Type | Specifications | Application | Standard |
|---|---|---|---|
| RVVP Shielded Cable | 3×1.0mm² (power/signal/ground) | Commercial/residential backbone | GB/T 5023-2008 |
| FPLP Flame-Retardant Cable | 18AWG (2.0mm²) LSZH | High-rise building shafts | NFPA 70 Article 760 |
| J-YSTY Telephone Cable | 2×0.8mm² twisted pair | Traditional alarm panel interconnect | EN 50200 |
2. Core Performance Indicators
2.1 Electrical Characteristics
- Conductor resistance:≤36Ω/km (at 20℃)
- Insulation resistance:≥100MΩ·km (500V DC)
- Withstand voltage:1500V AC/1min no breakdown
2.2 Physical Characteristics
- Operating temperature:-30℃~70℃
- Bending radius:≥6×cable diameter
- Tensile strength:≥80N/mm²
3. Cable Selection by Protocol
3.1 Traditional Dry Contact Interconnect
- 3-core cable:
- Red:12-24V DC power (16AWG)
- Black:COM common terminal
- Yellow:Signal transmission (requires shielding)
3.2 Digital Bus Systems (e.g. Honeywell Notifier)
- Requirements:
- Twisted pair (22AWG)
- Characteristic impedance 120Ω
- Capacitance ≤50pF/m
3.3 Power over Alarm (PoA)
- Composite cable:
- Power:18AWG×2
- Data:24AWG twisted pair
- UL 1424 certification required
4. Installation Standards
4.1 Wiring Distance Limits
- Unshielded cable:≤100m (24V system)
- Shielded twisted pair:≤300m (RS-485 protocol)
- Fiber optic conversion:up to 2km (OM1 multimode required)
4.2 Construction Requirements
- Separation from power lines:
- Parallel runs ≥300mm
- Crossings ≥100mm
- Conduit fill ratio:≤40% cross-section
- Termination:Crimped gold-plated terminals required
5. Recommended Brands/Models
5.1 Commercial Grade
- Panduit F1XT Series
- CommScope FIREGUARD
5.2 Residential Grade
- Putian Building Intelligence Cable
- Siemon F3 Series
6. Frequently Asked Questions
Q:Can Ethernet cable be used as substitute?
A:Only Cat5e+ shielded twisted pair meeting:
- Conductor size ≥24AWG
- DC resistance ≤9.38Ω/100m
- UL 2196 fire test certification
Q:How to select cables for retrofit projects?
A:Recommended options:
- Armored flat cable (surface mounting)
- FPLR cable with self-adhesive shielding
- Compliant with GB/T 19666-2019 flame retardant standard
Note: Critical areas require redundant wiring (ring/star topology). All cables must pass:
- Continuity test (≤1Ω loop resistance)
- Insulation test (≥500MΩ@500V DC)
- Protocol compliance test (e.g. LPCB certification for EST3 systems)